VMP and Vent PRO – Explosion venting devices
The RSBP membrane is the perfect economical solution for protection against damage and loss in production caused by the explosion. Under normal operating conditions, the venting opening on the technological equipment is covered by the explosion venting panel. When the operating pressure level increases inside the device, the venting panel opens, and thus the pressure and flame are released from the protected space. The technology is exposed to a lower pressure than its pressure resistance and hence won’t be destroyed. Effective dust explosion venting, including light metal dust, gas, and hybrid mixtures. Explosion venting device VMP is certified according to EN 14797 standard.
Where is the risk?
Dust storage and handling in the industry are often associated with a real risk of explosion. All you need is a spark from a short circuit in the electrical installation, a hot object that enters the technological unit together with the material, or a simple non-compliance with work safety – the consequences can be devastating. The risk of explosion arises not only when handling dust but also gas, steam, and hybrid mixtures.
WHERE IS THE RISK?
In industrial plants, there is a risk of explosion of dust, gas, flammable liquids, and their mixtures. The highest risk is in the food and pharmaceutical industry where, with regard to hygienic standards, only certain types of explosion protection equipment can be installed. The risk of endangering human life or health by explosion arises in case of increased movement of personnel around the production technology.
ADVANTAGES OF THE HRD SYSTEM
- quick system response
- high reliability
- suitable for indoor and outdoor applications
- a suitable solution for toxic and otherwise dangerous materials
- independent storage of data from detectors
- variability of components, simple and quick replacement after activation
- easy handling and transport
- application for dust up to St 3 class, light metals dust, hybrid mixtures, and gases
- suitable for technologies with increased demands on hygienic requirements (food industry, pharmaceutical industry, etc.)
- possibility of installation on equipment with different operating processes (vibration process, high temperature, etc.)
SUITABLE FOR
- filters and filtration units
- industrial vacuum cleaners
- silos
- mills
- dryers
- cyclones
- conveyors
- powder containers
- elevators
- mixers
- crushers
- and other industrial equipment
VMP F
Type | Vent area (m2) | A – external dimension (mm) | B – external dimension (mm) |
229 x 229 F | 0,05 | 309 | 309 |
229 x 305 F | 0,06 | 309 | 385 |
260 x 260 F | 0,07 | 337 | 337 |
170 x 470 F | 0,08 | 250 | 550 |
220 x 540 F | 0,12 | 308 | 628 |
270 x 458 F | 0,12 | 350 | 538 |
305 x 457 F | 0,14 | 390 | 542 |
300 x 500 F | 0,15 | 382 | 589 |
410 x 410 F | 0,17 | 490 | 490 |
241 x 762 F | 0,18 | 331 | 852 |
630 x 310 F | 0,19 | 385 | 705 |
580 x 410 F | 0,24 | 500 | 670 |
490 x 590 F | 0,28 | 573 | 673 |
610 x 470 F | 0,29 | 550 | 690 |
600 x 600 F | 0,35 | 656 | 656 |
450 x 800 F | 0,36 | 550 | 900 |
610 x 610 F | 0,37 | 690 | 690 |
500 x 750 F | 0,38 | 580 | 830 |
457 x 890 F | 0,39 | 537 | 970 |
586 x 920 F | 0,53 | 671 | 1005 |
588 x 908 F | 0,53 | 680 | 1000 |
800 x 800 F | 0,62 | 850 | 850 |
685 x 1100 F | 0,75 | 765 | 1178 |
870 x 910 F | 0,79 | 960 | 1000 |
920 x 920 F | 0,83 | 1005 | 1005 |
915 x 1118 F | 1,02 | 1000 | 1203 |
1020 x 1020 F | 1,03 | 1106 | 1106 |
1118 x 1118 F | 1,25 | 1202 | 1202 |
1130 x 1130 F | 1,28 | 1220 | 1220 |
1000 x 2000 F | 2,00 | 1090 | 2090 |
VMP D
Type | Vent area (m2) | A – external dimension (mm) | B – external dimension (mm) |
229 x 229 D | 0,05 | 309 | 309 |
260 x 260 D | 0,06 | 340 | 340 |
150 x 600 D | 0,08 | 220 | 670 |
220 x 540 D | 0,11 | 300 | 620 |
305 x 457 D | 0,12 | 375 | 527 |
610 x 290 D | 0,16 | 365 | 685 |
630 x 310 D | 0,18 | 385 | 705 |
490 x 590 D | 0,27 | 565 | 665 |
450 x 800 D | 0,34 | 530 | 880 |
586 x 920 D | 0,51 | 661 | 995 |
2 x 610 x 290 D | 0,32 | 385 | 1385 |
2 x 630 x 310 D | 0,35 | 385 | 1385 |
920 x 920 D | 0,81 | 995 | 995 |
915 x 1118 D | 0,98 | 990 | 1193 |
1020 x 1020 D | 1,00 | 1095 | 1095 |
VENT PRO S
Type | Vent area (m2) | A – external dimension (mm) | B – external dimension (mm) |
229 x 229 S | 0,05 | 309 | 309 |
260 x 260 S | 0,07 | 340 | 340 |
220 x 540 S | 0,12 | 300 | 620 |
305 x 457 S | 0,14 | 390 | 542 |
340 x 440 S | 0,15 | 400 | 500 |
610 x 290 S | 0,17 | 365 | 685 |
630 x 310 S | 0,19 | 385 | 705 |
490 x 590 S | 0,28 | 565 | 665 |
450 x 800 S | 0,36 | 530 | 880 |
578 x 851 S | 0,47 | 658 | 931 |
586 x 920 S | 0,53 | 661 | 995 |
920 x 920 S | 0,84 | 995 | 995 |
851 x 1162 S | 0,98 | 931 | 1242 |
915 x 1118 S | 1,01 | 990 | 1193 |
1020 x 1020 S | 1,01 | 1095 | 1095 |
1130 x 1130 S | 1,28 | 1220 | 1220 |
VMP SU – rectangular
Type | Vent area (m2) | A – external dimension (mm) | B – external dimension (mm) |
229 x 229 SU | 0,04 | 309 | 309 |
260 x 260 SU | 0,05 | 340 | 340 |
220 x 540 SU | 0,10 | 300 | 620 |
305 x 457 SU | 0,11 | 375 | 527 |
610 x 290 SU | 0,14 | 365 | 685 |
630 x 310 SU | 0,16 | 385 | 705 |
490 x 590 SU | 0,24 | 565 | 665 |
2 x 610 x 290 SU | 0,28 | 385 | 1385 |
450 x 800 SU | 0,32 | 530 | 880 |
2 x 630 x 310 SU | 0,35 | 385 | 1405 |
586 x 920 SU | 0,48 | 661 | 995 |
920 x 920 SU | 0,78 | 995 | 995 |
915 x 1118 T | 0,95 | 990 | 1193 |
1020 x 1020 T | 0,96 | 1092 | 1095 |
VMP SU – rounded
Type | Vent area (m2) | D1 – Dimension of a hole in technology (mm) | D2 – Pitch circle (mm) | D3 – External dimension (mm) |
DN 250 | 0,05 | 265 | 320 | 345 |
DN 300 | 0,06 | 315 | 350 | 375 |
DN 350 | 0,07 | 340 | 387 | 420 |
DN 400 | 0,10 | 390 | 443 | 475 |
DN 450 | 0,13 | 445 | 486 | 525 |
DN 510 | 0,16 | 505 | 550 | 585 |
DN 600 | 0,24 | 595 | 646 | 675 |
DN 630 | 0,27 | 625 | 680 | 705 |
DN 750 | 0,41 | 765 | 817 | 845 |
DN 800 | 0,47 | 815 | 860 | 895 |
DN 880 | 0,53 | 875 | 920 | 955 |
DN 900 | 0,57 | 895 | 955 | 995 |
DN 1000 | 0,72 | 995 | 1060 | 1095 |
DN 1100 | 0,87 | 1095 | 1160 | 1195 |